INSPECTION CHECKLIST - General


EXTERIOR:

Fire Lanes marked/unobstructed – MSFC 503.3 & 503.4
Address visible – MSFC 505.1
Fire hydrants/water supply accessible – MSFC 508
Combustible accumulations/storage acceptable – MSFC 304.2, MSFC 315.3
F.D. keybox present – MSFC 506.1
F.D. connections visible/good condition – MSFC 912
Gas meter/piping protected against impact – MSFC 603.9, 312.1

EXIT FEATURES/MEANS OF EGRESS:

Adequate number of exits – MSFC 1004.4, MSFC 1015, MSFC 1019, MSFC 1027.23
Exits, aisles, & corridors free of obstructions – MSFC 1028.3
Exit doors openable from inside – MSFC 1008.1.8.3
Exit signs present – MSFC 1011, MSFC 1027.3
Emergency lighting present & operational – MSFC 1006, MSFC 1027.5
Interior finish acceptable – MSFC 803, MSFC 804
Exit corridors rated/sprinklered – MSFC 1017.1, MSFC 1027.17

CONSTRUCTION FEATURES:

Fire rated construction present/maintained – MSFC 703.1
Hazardous (incidental use) areas separated/sprinklered – MSFC 705.3
Rated fire doors operational – MSFC 703.2
Vertical openings protected/sprinklered – MSFC 704.2

STORAGE:

Storage neat and orderly – MSFC 315.2
Combustible storage prohibited in boiler, mechanical and electrical equipment rooms – MSFC 315.2.3
Attic storage – MSFC 315.2.4
Combustible storage prohibited under enclosed stairways – MSFC 1009.5.3
Storage maintained 2’ below ceiling (unsprinklered)/18” (sprinklered) – MSFC 315.2.1
Rubbish containers >40 gals have lids & are non-combustible – DELETED
Oily rags protected against spontaneous ignition – MSFC 305.2
Decorations to be flame resistant in Assembly Occ. (foams, curtains, drapes, hangings) – MSFC 807.4.2

FLAMMABLE/COMBUSTIBLE LIQUIDS:

Safety containers if used – MSFC 3405.2.4
Not stored/kept near exits – MSFC 3404.3.3.3
No sources of ignition – MSFC 3404.2.4, 3405.3
Quantities >10 gals in cabinet – MSFC 3404.3.4.2, MSFC 3404.3.4.4

UTILITY/MECHANICAL/HVAC:

Shut off valves present on gas appliances – MSFC 603.1
Approved piping, connections & appliances used – MSFC 603.1.2
Combustion air supply/venting present – MSFC 603.4, 603.7
Adequate clearance between combustibles and appliances – MSFC 603.1, MSFC 305.1
Ducts and filters are clean – MSFC 904.11.6.3

FIRE EXTINGUISHERS:

Readily accessible – MSFC 906.6
Travel distance of 75’ (or sprinklered) – MSFC 906.1
Tested/inspected annually – MSFC 901.6.1

SPRINKLER SYSTEM:

Coverage is adequate – MSFC 903.3.1
Controls are readily accessible – MSFC 903.3.1
Valves locked open – MSFC 903.4.4
System and valves supervised (>20 sprinklers, 100 in existing) – MSFC 903.4
Heads in good condition – MSFC 903.3.1
Wrench/spare sprinklers present – MSFC 903.3.1
Tested/inspected annually – MSFC 901.6
Riser/pump rooms labeled – MSFC 510.1

FIRE ALARM & DETECTION SYSTEMS:

Control panel & annunciator panel in normal condition (no trouble or alarm conditions) – MSFC 901.4.1, 901.7
Detectors properly installed – MSFC 907
Tested/inspected annually – MSFC 907.20

OTHER FIRE PROTECTION SYSTEMS:

Standpipes needed (>50 ft.) – MSFC 905.11
Standpipes/hose in good condition – MSFC 905.2
Adequate coverage – MSFC 905.2
Hood system-fuel shutoff present – MSFC 904.11.2
Properly services/maintained – MSFC 904.11.6

ELECTRICAL:

Proper wiring/connections – MSFC 605.1, 605.6
Appliances/fixtures in good condition – MSFC 605.7
Overcurrent protection present – MSFC 605.1
Power taps not used – MSFC 605.4
Extension cords not a substitute for fixed wiring – MSFC 605.5
Power strips properly used – MSFC 605.4
Access to electrical panels provided – MSFC 605.3

HAZARDOUS MATERIALS:

Compressed gas cylinders secured – MSFC 3003.5
Rooms/areas properly labeled – MSFC 2703.5
Acceptable quantities – MSFC 2703.1.1
Separation of incompatible materials – MSFC 2703.9.8

This checklist is intended as a guide to assist fire inspection personnel in identifying common fire and life safety hazards. It does not list all possible code requirements. Please see other checklists for information on other occupancies/topics.